Verbinden met een Sunny TriPower omvormer met groot scherm en (netbewakings-) parameters aanpassen via RS485 en een Sunny WebBox (België).
August 2017
Voor installaties met een Sunny WebBox hebt u geen extra programma nodig.
1. Inloggen in de Sunny WebBox
Log rechtstreeks aan in de WebBox als ‘Installer’ en selecteer een omvormer waarvan u de waarden wilt wijzigen. Ga naar de parameter pagina.

2. De netbewakingsparameters wijzigen naar Belgische normen
2.1 Grid Guard code
Vooraleer de installateur netbewakingsparameters kan gaan wijzigen, moet deze zijn/haar Grid Guard code ingeven in de WebBox. Geef uw SMA Grid Guard code in bij de parameter ‘Inst.Code’.

Nadat u de Grid Guard code heeft opgeslagen kan u de nodige net parameters wijzigen.
2.2 De netbewakingsparameters wijzigen
Zorg er eerst voor dat de omvormer ingesteld staat op de juiste landinstellingen. Selecteer bij ‘Landnorm instellen’ de ‘C10/11’ norm.
Pas hierna de parameter ‘VolCtl.Rpro’ aan naar 253 V en ‘VolCtl.h.Lim’ naar 264,5 V.
Vergeet niet op te slaan!